HRX-OM-W002-A
Chapter 3 Transport and Setting Up
HRR Series
3.4 Piping
3-21
5.
In case of water-cooled type, please also connect the piping of the facility water inlet
and outlet of the
customer’s water source equipment.
Recommended piping circuit
Fig.
3-10
Recommended piping circuit
№
Description
Size
1
Valve
Rc1/2
2
Pressure gauge
0 to 1.0MPa
3
Pipe,hose,etc.
inside diameter
Φ15 or more
Thermo-chiller
Circulating fluid
return port
Circulating fluid
outlet
Facillity water outret
(Water-cooled refrigeration)
Facillity water inlet
(Water-cooled refrigeration)
User's
equipment
1
1
1
1
1
1
2
Facility
water
branch
1
Tightening
torque
Rc1/2
:
28 to 30N
・
m
Rc3/8
:
22 to 24N
・
m
To the inlet
へ
From the outlet
From the user
’s
water source outlet
To the user
’s
water source inlet
Circulating fluid outlet
Rc1/2
Circulating fluid Return port
Rc1/2
Facility water inlet
Rc3/8
Facility water outlet
Rc3/8