HRX-OM-W002-A
Chapter 5 Display and Setting of Various Functions
HRR Series
5.5 Advanced setting mode
5-27
[11]
"Add output of temperature range upper limit alarm": Set to "OFF".
[12]
"Temperature range lower limit alarm switching": Set to "OFF".
[13]
"Add output of temperature range lower limit alarm": Set to "OFF".
State
①
: Start of operation "30 sec" elapsed, alarm notice as the bandwidth is not reached in
time.TEMP OUT signal ON.
State
②
: Although it is within the bandwidth range, since the "stable time of TEMP READY" has not
elapsed, the alarm continues,TEMP OUT signal ON state continues.
Statu
③
: Stable time "60 sec" elapsed, TEMP OUT signal OFF. READY signal ON.
State
④
: Manual reset of alarm. Since the alarm cancellation condition is entered, the alarm OFF.
State
⑤
: Although it is out of band width, READY signal continues as "READY is out of time".
State
⑥
: Time when READY disappears after "30 sec" has elapsed, the READY signal OFF, alarm
report, TEMP OUT signal ON.
State
⑦
: Manual reset of alarm. Since the alarm cancellation condition is not entered, the alarm ON
continues.
State
⑧
: Stable time "60 sec" elapsed, TEMP OUT signal OFF. READY signal ON.
TEMP READY bandwidth lower limit
17.
Press the [
▼] key. Displays TEMP READY bandwidth lower limit setting screen.
RUN
℃
READY
⇒
LBAND
(
Alternately displayed
)
TEMP READY bandwidth lower limit
(
Setting range
:
-0.1 to -9.9
℃
)
Chiller
Operation
Stop
Circulating fluid
setting temperature 15.0 ° C
TEMP READY signal
ON
OFF
READY
Bandwidth
(upper limit) 17.0 ° C
READY
Bandwidth
(Lower limit) 13.0 ° C
60s
③
NOT TEMP READY
alarm
Generation
Without
Elapsed time
30s
②
30s
④
①
⑥
TEMP OUT signal
(When READY
output is set)
ON
OFF
Alarm manual reset
⑤
Alarm manual reset
⑦
⑧
60s
Содержание HRR012-A*-20 Series
Страница 14: ...HRX OM W002 A Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Страница 110: ...HRX OM W002 A Chapter 5 Display and Setting of Various Functions 5 5 Advanced setting mode HRR Series 5 62...
Страница 138: ...HRX OM W002 A Chapter 8 Control Inspection Exchange and Cleaning 8 5 Electrical schematic diagram HRR Series 8 18...
Страница 156: ...HRX OM W002 A Chapter 9 Documents 9 9 Daily Check HRR Series 9 18...
Страница 159: ......