HGMS62 Split Type Genset Controller User Manual Page 7 of 58
Each phase and total active power P kW
Reactive power Q kvar
Apparent power S kVA
Power factor PF
Gen accumulated energy kWh, kvarh, kVAh
Load output PCT (active power/rated power)x100%
—
With over/under voltage, over/under frequency, loss of phase, reverse phase sequence
functions of mains; with over/under voltage, over/under frequency, over current, over power,
reverse power, loss of phase and reverse phase sequence functions of gen;
—
Precise measure and display of various parameters of engine:
Temp. (WT) °C/ °F
Oil pressure (OP)
kPa/psi/bar
Fuel level (FL) %
Speed (SPD)
r/min (RPM)
Battery Voltage (VB) V
Charger D+ Voltage (VD) V
Accumulated running hours Up to 65535 hours
Accumulated start times Up to 65535 times
—
Control protection: automatic start/stop of genset, closing/opening (ATS transfer) and perfect
failure display and protection functions;
—
With ETS, idle speed control, pre-heat control, speed drop/raise control, all of them are relay
outputs;
—
Parameter setting: allow users to modify setting, parameters cannot be lost even when power
off. Most of parameters can be set from the front panel, all parameters can be adjusted via USB
interface (or RS485 interface) of PC.;
—
A variety of temperature, pressure and fuel level sensor curves can be used directly, and can be
defined by users; pressure, config.2 can be connected to resistance, voltage or current type
sensor;
—
Multiple conditions of crank disconnect (frequency, speed, oil pressure) can be selected;
—
Wide power supply range: DC(8~35)V, adapting to different starting battery volts;
—
Event log, RTC, scheduled start/stop (once a month/week/day can be set whether to take load
or not);
—
With data record functions of mains voltage/frequency, gen voltage/frequency, current,
temperature, oil pressure, fuel level, speed, etc. 1min before stop failure, max 5 pieces can be
recorded;
—
Can be used for water pump unit, also can be used as indication instrument (only indication,
alarm, no action for relay);
—
With maintenance function. Maintenance time or actions (only warning or trip shutdown or
alarm shutdown) can be set;
—
Add rubber gasket between HGMS62D shell and panel, protection level can reach IP65;
—
HGMS62D is fixed by metal fixing clips and HGMS62M is fixed with screws;
—
Modular design and pluggable terminal, compact structure and easy installation;
—
Personalized startup interface, customers can define it as demand and display via HGMS62D.