![Smartgen HGMS62 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/smartgen/hgms62/hgms62_user-manual_1297538026.webp)
HGMS62 Split Type Genset Controller User Manual Page 26 of 58
No.
Items
Range
Default
Description
Timer Setting
1
Start Delay
(0-3600)s
1
Time from mains abnormal or remote
start signal active to genset start.
2
Stop Delay
(0-3600)s
1
Time from mains normal or remote start
signal inactive to genset stop.
3
Preheat Time
(0-3600)s
0
Pre-power time of heater plug before
starter is powered.
4
Crank Time
(3-60)s
8
Every starter power-on time.
5
Crank Rest Time
(3-60)s
10
Wait time before secondary power-on
begins when engine crank fails.
6
Safety Run Time
(0-3600)s
10
Low oil pressure, high temperature,
under speed, under frequency, under
voltage, charge failure alarms are
inactive during the period.
7
Start Idle Time
(0-3600)s
0
Genset idle running time when starting.
8
Warming Up Time
(0-3600)s
10
Warming up time before closing after
genset entering high-speed running.
9
Cooling Time
(0-3600)s
10
Cooling time before stopping after
genset off-load.
10
Stop Idle Time
(0-3600)s
0
Genset idle running time when stopping.
11
ETS Time
(0-3600)s
20
Stop solenoid power-on time when
stopping.
12
Wait for Stop Time
(0-3600)s
0
Time from idle delay over to stop
completely when “ETS Time” is 0; Time
from ETS delay over to stop completely
when “ETS Time” is not 0.
13
After Stop Time
(0-3600)s
0
Time from complete stop to standby.
14
Raise Speed Pulse
Time
(0-20.0)s
1.0
Raise speed pulse output time when
genset entering warming up.
15
Drop Speed Pulse
Time
(0-20.0)s
1.0
Drop speed pulse output time when
genset entering stop idle.
16
Smart Preheat
(0-1)
0
0: Disable; 1: Enable.
17
Smart Preheat Sensor (0-4)
0
0: Temperature Sensor; 1: Aux. Sensor 1;
2: Aux. Sensor 2; 3: Oil Pressure Sensor;
4: Fuel Level Sensor.
18
Sensor Set Value
(0-1000)
40
19
Fuel Output Time
(0-3600)s
1
Pre-fuel output time before starter is
powered on.
Engine Setting
1
Type
(0-69)
0
Default: 0 Non-ECU.