HGMS62 Split Type Genset Controller User Manual Page 42 of 58
No.
Type
Function Description
10
Inhibit Auto Start
After input is active in auto mode, genset auto start is inhibited.
11
Inhibit Scheduled Start
After input is active in auto mode, genset scheduled start is
inhibited.
12
Reserved
13
Aux. Gen. Closed
Connect the auxiliary contactor of generator loading switch.
14
Gen. On-load Inhibit
When input is active, genset will inhibit to close.
15
Aux. Mains Closed
Connect the auxiliary contactor of mains loading switch.
16
Mains On-load Inhibit
When input is active, mains will inhibit to close.
17
Auto Mode Input
When input is active, controller will enter into auto mode, and other
keys on the panel are inactive except for
, and
displays on LCD status page.
18
Auto Mode Inactive
When input is active, controller will not work in auto mode,
key is unavailable.
19
Reserved
20
Reserved
21
Inhibit Alarm Shutdown
All shutdown alarms are inhibited except for emergency stop (also
called Battle Mode or Override Mode)
22
Instrument Mode
All outputs are inhibited in this mode.
23
Box
Temp
High
Warning
When input is active, it means box temperature high warning alarm
is issued.
24
Reset
Maintenance
Time
When input is active, controller will reset maintenance time and
date as pre-set values.
25
Low Level Shutdown
Connect to sensor digital input.
26
High Temp Shutdown
Connect to sensor digital input.
27
Low OP Shutdown
Connect to sensor digital input.
28
Remote Start (On-load)
When input is active in auto mode, genset will start automatically,
and then genset takes on load after normal running. When input is
inactive, genset will stop automatically.
29
Remote Start (Off-load)
When input is active in auto mode, genset will start automatically
without taking load after normal running. When input is inactive,
genset will stop automatically.
30
Manual Start Input
When input is active in manual mode, genset will start
automatically. When input is inactive, genset will stop
automatically.
31-39 Reserved
40
Raise Speed Pulse
When engine type is 35 MTSC1 and is active, the target engine
speed increases 50RPM.
41
Drop Speed Pulse
When engine type is 35 MTSC1 and is active, the target engine
speed decreases 50RPM.
42
Idle Pulse Input
When engine type is 35 MTSC1 and is active, the target engine