No.
Items
Range
Default
Description
(-50-300)ºC
75
Return value: when external temperature
value is more than or equal to it, warning
will be removed.
(0-3600)s
5
Confirm time for low temperature
warning detection.
6
Heater Control
(0-1)
0
0: Disable; 1: Enable.
(-50-300)ºC
50
When external temperature value is
more than or equal to it, coolant heating
control outputs.
(-50-300)ºC
55
Return value: when external temperature
value is more than or equal to it, coolant
heating will stop.
(0-3600)min
60
Coolant heating control output time.
7
Cooler Control
(0-1)
0
0: Disable; 1: Enable.
(-50-300)ºC
80
When external temperature value is
more than or equal to it, coolant heating
control outputs.
(-50-300)ºC
75
Return value: when external temperature
value is less than or equal to it, coolant
heating will stop.
(0-3600)min
60
Coolant heating control output time.
Oil Pressure Sensor
1
Curve Type
(0-15)
8
SGD. See Table 16.
2
Open Action
(0-2)
0
0: Warning; 1: Shutdown; 2: None.
3
Over Low Shutdown
(0-1)
0
0: Disable; 1: Enable.
(0-1000)kPa
103
When external oil pressure value is lower
than it, low oil pressure shutdown alarm
will be issued. This value only begins to
judge after safety delay is over.
(0-3600)s
3
Confirm time for over low oil pressure
shutdown detection.
4
Over Low Warning
(0-1)
0
0: Disable; 1: Enable.
(0-1000)kPa
124
When external oil pressure value is lower
than it, low oil pressure warning will be
issued. This value only begins to judge
after safety delay is over.
(0-1000)kPa
138
Return value: when external oil pressure
value is more than or equal to this value,
alarm is removed.
(0-3600)s
5
Confirm time for over low oil pressure
warning detection.