![Smartgen HGMS62 Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/smartgen/hgms62/hgms62_user-manual_1297538025.webp)
HGMS62 Split Type Genset Controller User Manual Page 25 of 58
8
PARAMETER RANGE AND DEFINITION
8.1
PARAMETER CONTENT AND RANGE
Table 13 – Parameter Content and Range
No.
Items
Range
Default
Description
Mains Setting
1
Mains Enable
(0-1)
1
0: Disable; 1: Enable.
2
Supply System
(0-3)
0
0: 3P4W;
1: 3P3W;
2: 2P3W;
3: 1P2W.
3
Rated Voltage
(30-30000)V
230
Provide standard for mains over/under
voltage. If PT is used, this value is
transformer secondary voltage.
4
Rated Frequency
(10.0-75.0)Hz
50.0
Provides standard for mains over/under
frequency.
5
Normal Delay
(0-3600)s
10
Confirm time from mains abnormal to
normal.
6
Abnormal Delay
(0-3600)s
5
Confirm time from mains normal to
abnormal.
7
PT Setting
(0-1)
0
0: Disable; 1: Enable.
(30-30000)
100
Primary.
(30-1000)
100
Secondary.
8
Over Voltage Setting
(0-1)
1
0: Disable; 1: Enable.
(0-200)%
120
Set value: mains rated voltage PCT.
(0-200)%
116
Return value: mains rated voltage PCT.
(0-3600)s
5
Confirm time for over voltage detection.
9
Under Voltage Setting
(0-1)
1
0: Disable; 1: Enable.
(0-200)%
80
Set value: mains rated voltage PCT.
(0-200)%
84
Return value: mains rated voltage PCT.
(0-3600)s
5
Confirm time for under voltage
detection.
10
Over
Frequency
Setting
(0-1)
0
0: Disable; 1: Enable.
(0-200)%
114
Confirm time for over freq. detection.
(0-200)%
110
Confirm time for over freq. detection.
(0-3600)s
5
Confirm time for over freq. detection.
11
Under
Frequency
Setting
(0-1)
0
0: Disable; 1: Enable.
(0-200)%
90
Confirm time for over freq. detection.
(0-200)%
94
Confirm time for over freq. detection.
(0-3600)s
5
Confirm time for under freq. detection.
12
Loss of Phase Setting (0-1)
1
0: Disable; 1: Enable.
13
Reverse Phase Setting (0-1)
1