![Smartgen HGMS62 Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/smartgen/hgms62/hgms62_user-manual_1297538040.webp)
HGMS62 Split Type Genset Controller User Manual Page 40 of 58
No.
Type
Function Description
158-
229
Reserved
230
Stop Mode
Action when system in stop mode.
231
Manual Mode
Action when system in manual mode.
232
Reserved
Reserved
233
Auto Mode
Action when system in auto mode.
234
Gen On-load Indication
Outputs when gen is closed.
235
Mains On-load Indication Outputs when mains is closed.
236
Reserved
237
Reserved
238
Reserved
239
Reserved
8.2.2
CUSTOM PERIOD OUTPUT
Custom period output includes: period output S1 and condition output S2.
S1 and S2 are both
TRUE
, it outputs;
S1 or S2 is
FALSE
, it doesn’t output;
Period output S1
can set generator’s one or more period outputs freely, can set the delayed time
and output time after entering into period.
Condition output S2
can be set as any contents in output ports.
NOTE1:
When delay time and output time both are 0 in period output S1, it is TRUE in this period.
NOTE2:
When selected period is standby, it is cycle output, and other periods are single output.
For example:
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: input port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);
Output port 1 active, after enter “start time” and delay 2s, the custom period output is outputting, after 3s, stop
outputting;
Output port 1 inactive, custom output period is not outputting
8.2.3
CUSTOM COMBINATION OUTPUT
Custom combination output is composed by 3 parts,
or
condition output S1, or
condition output S2
,
and condition output S3
.