COMMISSIONING
Before operation, the following checkings should be carried out:
—
Check and ensure all the connections are correct and wires diameter is suitable.
—
Ensure that the controller DC power has fuse; battery positive and negative have correctly
connected.
—
Take proper actions to prevent engine to disconnect crank (e.g. Remove the connections of fuel
value). If checking is OK, connect starting battery, select Manual Mode, controller will execute the
program.
—
Set controller as Manual Mode, press “start” button to start genset. If fails within the setting crank
times, controller will send “Fail to Start” signal; then press “stop” to reset controller.
—
Recover actions of preventing engine to disconnect crank (e. g. Connect wire of fuel value), press
“start” button again, genset will start. If everything goes well, genset will normally run after idle
running (if configured). During this period, watch for engine’s running situations, voltage and
frequency of alternator. If there is abnormal situation, stop genset and check all connections
according to this manual.
—
Select the Auto Mode from front panel and connect mains signal. After mains normal delay,
controller will transfer ATS (if configured) to mains on-load. After cooling time, it will stop to enter
standby status unit mains has abnormal situations again.
—
When mains is abnormal again, genset will start automatically to enter normal running status, then
close gen command is issued, ATS is controlled to genset on-load. If not, please check all
connections according to this manual.
—
If there are any other questions, please contact SmartGen’s service.