HGMS62 Split Type Genset Controller User Manual Page 28 of 58
No.
Items
Range
Default
Description
(0-200)%
90
Return value: battery rated volt PCT.
(0-3600)s
60
Confirm time for battery under volt
detection.
15
Charge Failure
(0-1)
1
0: Disable; 1: Enable.
(0-60.0)V
8.0
Set value: Charge failure warning is
issued when charger D+(WL) voltage is
lower than this value during genset
normal running.
(0-60.0)V
10.0
Return value: Warning is removed when
charger D+(WL) voltage value is higher
than this value.
(0-3600)s
10
Confirm time for charge failure detection
16
Crank Times
(1-10)times
3
Max crank times for engine.
When the set crank times is reached,
controller will issue crank failure warning
17
Crank
Disconnect
Conditions
(0-6)
2
See Table 17.
There are 3 conditions for starter and
engine disconnect, which can be used
separately or together, aiming at
disconnecting starting motor and engine
as soon as possible.
18
Crank
Disconnect
Frequency
(0-200)%
24
Set value is percentage of gen rated
frequency. When gen frequency is higher
than it, starter will be disconnected, see
following installation description.
19
Crank
Disconnect
Speed
(0-200)%
24
Set value is percentage of gen rated
speed. When speed is higher than it,
starter will be disconnected, see
following installation description.
20
Crank Disconnect OP
(0-1000)kPa
200
When oil pressure is higher that set
value, starter will be disconnected, see
following installation description.
21
CAN Vaud Rate
(0-1)
0
0: 250bps; 1: 500bps.
22
TSC1 Source Address
(0-255)
3
When engine type is GTSC1 PLUS, this
item is active.
23
Charge Volt Sampling
(0-1)
0
0: Controller; 1: ECU
24
Engine
Temp
Sampling
(0-1)
1
0: Controller; 1: ECU
25
OP Sampling
(0-1)
1
0: Controller; 1: ECU
26
Battery Under Volt
Start
(0-1)
0
0: Disable; 1: Enable.