![Smartgen HGMS62 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/smartgen/hgms62/hgms62_user-manual_1297538022.webp)
HGMS62 Split Type Genset Controller User Manual Page 22 of 58
No.
Function
Size
Remarks
36
R OUT
1.5mm
2
Mains R phase monitoring outputs after passing the
fuse.
37
Mains R Phase Voltage
Monitoring Input
1.5mm
2
Connect mains R phase, 10A fuse is used for
controller.
38
Mains S Phase Voltage
Monitoring Input
1.0mm
2
Connect mains S phase, 10A fuse is used for
controller.
39
Mains T Phase Voltage
Monitoring Input
1.0mm
2
Connect mains T phase, 10A fuse is used for
controller.
40
Mains N1 Line Input
1.0mm
2
Connect mains N line.
41
U OUT
1.5mm
2
Genset U phase monitoring outputs after passing the
fuse.
42
Genset U Phase Voltage
Monitoring Input
1.5mm
2
Connect U phase of genset output, 10A fuse is used
for controller.
43
Genset V Phase Voltage
Monitoring Input
1.0mm
2
Connect V phase of genset output, 10A fuse is used
for controller.
44
Genset W Phase Voltage
Monitoring Input
1.0mm
2
Connect W phase of genset output, 10A fuse is used
for controller.
45
Genset N2 Line Input
1.0mm
2
Connect N line of genset output.
Connector A (Connect to HGMS62D)
1
B+ IN
1.5mm
2
Connect terminal 6 (B+ OUT) to this terminal through
a power switch to supply for positive of HGMS62M.
2
B+ OUT1
1.5mm
2
Supply power to positive of HGMS62D.
3
B-
1.5mm
2
Negative of controller power.
4
RS232 RXD
0.5mm
2
RS232 communication port is connected with
HGMS62D.
Shielding line is required, shielded layer is connected
to terminal 7 GND.
5
RS232 TXD
0.5mm
2
6
B+ OUT
1.5mm
2
Main terminal 2 (DC B+) is connected to this terminal
after passing the fuse.
7
GND
0.5mm
2
The internal part is connected with negative of
controller.
8
EM.STOP OUT
1.5mm
2
Emergency input connect to external emergency
stop button.
9
EM.STOP IN
1.5mm
2
Connector B (Connect to ESC)
1
Fuel Relay Output
1.5mm
2
B+ is supplied by 2 points, rated 10A.
Connect to positive of ESC power.
2
MP1 Speed Output
0.5mm
2
The controller inside is connected to speed sensor of
Main terminal 26. Connect to speed sampling
terminal of ESC.
3
GND
1.5mm
2
The controller inside has connected to B-.
4
MP2 Speed Output
0.5mm
2
The controller inside has connected to B-.
5
NC