HGM8151 Genset Parallel Controller User Manual Page 27 of 66
No.
Items
Parameters
Defaults
Description
Pressure
set value, starter will be disconnected. See
the installation instruction.
Generator Setting
1
AC System
(0~3)
0
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
2
Poles
(2-64)
4
Numbers of generator pole, used for
calculating starter rotate speed when
without speed sensor.
3
Rated Voltage
(30~30000)V
230
To offer standards for detecting of gens’
over/under voltage and loading voltage. (It
is primary voltage when using voltage
transformer).
4
Loading Voltage
(0~200)%
90
Setting value is percentage of generator
rated voltage. When gens voltage under
load voltage, won’t enter
normally running,
during the period of when controller ready
to detect loading.
5
Rated Frequency
(10.0-75.0)Hz
50.0
To offer standards for detecting of
over/under/load frequency.
6
Loading Frequency
(0~200)%
90
Setting value is percentage of generator
rated frequency. When generator frequency
under load frequency, it won’t enter
normal
running.
7
Volt. Trans.(PT)
(0~1)
0
0: Disable; 1:Enable
8
Over Volt. Shutdown (0~200)%
120
Setting value is percentage of generator
rated volt. Delay value (default: 3s) also can
be set.
9
Under
Volt.
Shutdown
(0~200)%
80
10 Over Freq. Shutdown (0~200)%
114
Setting value is percentage of generator
rated freq. Delay value (over frequency
default: 2s and under frequency default: 3s)
also can be set.
11
Under
Freq.
Shutdown
(0~200)%
80
12 Over Volt. Warn
(0~200)%
110
Setting value is percentage of generator
rated volt. Delay value (default: 5s) and
return value (over volt default: 108 and
under volt default: 86) also can be set.
13 Under Volt. Warn
(0~200)%
84
14 Over Freq. Warn
(0~200)%
110
Setting value is percentage of gens rated
freq. Delay value (default: 5s) and return
value (over frequency default: 108 and
under frequency default: 86) also can be
set.
15 Under Freq. Warn
(0~200)%
84
Generator Load Setting
1
Current Trans.
(5~6000)/5
500
The ratio of external CT