HGM8151 Genset Parallel Controller User Manual Page 40 of 66
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, Defined combination output is
not outputting.
7.3
DEFINED CONTENTS OF PROGRAMMABLE INPUT PORTS (ALL GND (B-) ACTIVE)
Table 14 Defined Contents of Programmable Input Ports
No.
Type
Description
0
Users Configured
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and shutdown after
hi-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
1
Reserved
2
Alarm Mute
Can prohibit “Audible Alarm” outpu
t when input is active.
3
Alarm Reset
Can reset shutdown alarm and trip alarm when input is active.
4
60Hz Active
Use for CANBUS engine and it is 60Hz when input is active.
5
Lamp Test
All LED indicators are illuminating when input is active.
6
Panel Lock
All buttons in panel is inactive except
and
there is in the right of first row in LCD when input is active.
7
Reserved
8
Idle Speed Active
Under voltage/frequency/speed protection is inactive.
9
Auto Stop Inhibit
In
Auto
mode, during generator normal running, when input is
active, prohibit generator shutdown automatically.
10
Auto Start Inhibit
In
Auto
mode, prohibit generator start automatically when input is
active.
11
Scheduled Run Inhibit
In
Auto
mode, prohibit fixed timing start genset when input is
active.
12
Reserved
13
Gen Closed Auxiliary
Connect generator loading switch’s Aux. Point.
14
Gen Load Inhibit
Prohibit genset switch on when input is active.
15
Reserved
16
Reserved
17
Auto Mode Lock
When input is active, controller enters Auto mode; mode selection
keys in the panel are inactive.
18
Auto Mode Inhibit
When input is active, control
ler won’t work under Auto m
ode key
and simulate auto key input does not work.
19
Static Parallel