HGM8151 Genset Parallel Controller User Manual Page 28 of 66
No.
Items
Parameters
Defaults
Description
2
Rated
Full-load
Current
(5~6000)A
500
Generator’s rated current, standard of loa
d
current.
3
Rated Power
(0-6000)kW
276
Generator’s
rated power, standard of load
power.
4
Overload Current
(0~200)%
120
Setting value is percentage of generator
rated full-load current. Delay value also can
be set as definite time limit or inverse time
limit.
5
Over Power
(0~200)%
110
Setting value is percentage of generator
rated active power. Delay value (default:
30s) and action (default: trip and stop) can
be set.
6
Reverse Power
(0~200)%
10
Setting value is percentage of generator
rated active power. Delay value (default:
10s) and action (default: trip and stop) can
be set.
7
Earth Fault
(0~1)
0
0: Disable 1: Enable.
8
Imbalance Current
(0~1)
0
0: Disable 1: Enable.
9
Loss of Excitation
(0~200)%
20%
Setting value is percentage of generator
rated reactive power. Delay value (default:
5s) and action (default: trip) can be set.
Switch Setting
1
Close Time
(0~20.0)s
5.0
Pulse width of mains/generator switch on.
When it is 0, means output constantly.
2
Open Time
(0~20.0)s
3.0
Pulse width of mains/ generator switch off.
Module Setting
1
Power On Mode
(0~2)
0
0:
Stop mode 1: Manual mode
2: Auto mode
2
Module Address
(1~254)
1
Controller’s
address
during
remote
monitoring.
3
Stop Bit
(0~1)
0
0: 2 stop bits; 1: 1 stop bit
4
Language
(0~2)
0
0: Simplified Chinese 1: English 2:
Others
5
Password
(0~65535)
00318
For entering parameters setting.
6
Temp. Unit Select
(0-1)
0
0:
℃
1:
℉
7
Pressure Unit Select (0-2)
0
0: kPa; 1: Psi; 2: Bar.
8
Unparallel
Mode
Enable
(0-1)
0
0: Disable; 1: Enable
9
Date and Time
Set the module’s date
and time.
10 Ethernet Enable
(0~1)
1
0: Disable; 1: Enable
All Ethernet setting changes (e.g. IP
address, Subnet mask) are active after