HGM8151 Genset Parallel Controller User Manual Page 16 of 66
NOTE:
The auxiliary close input should be configured necessarily and make sure the connection is correct.
5
PROTECTIONS
5.1
WARNING ALARMS
Warning alarms does not lead to shutdown when warning signal is detected.
Table 7 Warning Alarms
No.
Type
Description
1 Over Speed
When the controller detects that the engine speed has exceeded the
pre-set value, it will initiate a warning alarm.
2 Under Speed
When the controller detects that the engine speed has fallen below the
pre-set value, it will initiate a warning alarm.
3 Loss of Speed Signal
When the controller detects that the engine speed is 0 and the action
select “Warn”,
it will initiate a warning alarm.
4 Gen Over Frequency
When the controller detects that the genset frequency has exceeded the
pre-set value, it will initiate a warning alarm.
5 Gen Under Frequency
When the controller detects that the genset frequency has fallen below
the pre-set value, it will initiate a warning alarm.
6 Gen Over Voltage
When the controller detects that the generator voltage has exceeded
the pre-set value, the controller will initiate a warning alarm.
7 Gen Under Voltage
When the controller detects that the genset voltage has fallen below the
pre-set value, it will initiate a warning alarm.
8 Gen Over Current
When the controller detects that the genset current has exceeded the
pre-set value
and the action select “Warn”,
it will initiate a warning
alarm.
9 Fail to Stop
After “fail to stop” delay, if gen
-set does not stop completely, it will
initiate a warning alarm.
10
Charge Alternator
Failure
When the controller detects that charger voltage has fallen below the
pre-set value, it will initiate a warning alarm.
11 Battery Over Volt
When the controller detects that start battery voltage has exceeded the
pre-set value, it will initiate a warning alarm.
12 Battery Under Volt
When the controller detects that start battery voltage has fallen below
the pre-set value, it will initiate a warning alarm.
13 Maintenance Due
When count down time is 0 and the action select “Warn”,
it will initiate a
warning alarm.
14 Reverse Power
If reverse power detection is enabled, when the controller detects that
the reverse power value (power is negative) has exceeded the pre-set
value
and the action select “Warn”,
it will initiate a warning alarm.
15 Over Power
If over power detection is enabled, when the controller detects that the
over power value (power is positive) has exceeded the pre-set value and
the action select “Warn”,
it will initiate a warning alarm.
16 ECU Warn
If an error message is received from ECU via J1939, it will initiate a