HGM8151 Genset Parallel Controller User Manual Page 25 of 66
7
SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
7.1
CONTENTS AND SCOPES OF PARAMETER SETTING
Table 12 Parameter Setting Contents and Scopes
No.
Items
Parameters
Defaults
Description
Timer Setting
1
Start Delay
(0~3600)s
5
Time from remote start signal is active to
start genset.
2
Stop Delay
(0~3600)s
30
Time from remote start signal is inactive to
stop genset.
3
Preheat Delay
(0~3600)s
0
Time of pre-powering heat plug before
starter is powered up.
4
Cranking Time
(3~60)s
8
Time of starter power on
5
Crank Rest Time
(3~60)s
10
The waiting time before second power up
when engine start fail.
6
Safety On Delay
(0-3600)s
10
Alarms for low oil pressure, high
temperature, under speed, under frequency
/voltage, charge fail are inactive.
7
Start Idle Time
(0~3600)s
10
Idle running time of genset when starting.
8
Warming Up Time
(0~3600)s
30
Warming up time between genset switch on
and high speed running.
9
Cooling Time
(0~3600)s
60
Radiating time before genset stop, after it
unloads.
10
Stop Idle Time
(0~3600)s
10
Idle running time when genset stop.
11
ETS Solenoid Hold
(0~3600)s
20
Stop electromagnet’s power on time when
genset is stopping.
12
Fail to Stop Delay
(0~3600)s
0
Time between ending of genset idle delay
and stopped when “ETS time” is set as 0;
Time between ending of ETS hold delay and
stopped when “ETS Hold ou
tp
ut time” is not
0.
13
After Stop Time
(0~3600)s
0
Time between genset stopped and standby.
Engine Setting
1
Engine Type
(0~39)
0
Default: non-ECU.
When connected to J1939 engine, choose
the corresponding type.
2
Flywheel Teeth
(10~300)
118
Tooth number of the engine, for judging of
starter
separation
conditions
and
inspecting of engine speed. See the
installation instructions.
3
Rated Speed
(0~6000)r/min 1500
Offer standard to judge over/under/loading
speed.
4
Loading Speed
(0~100)%
90
Setting value is percentage of rated speed.