HGM8151 Genset Parallel Controller User Manual Page 30 of 66
No.
Items
Parameters
Defaults
Description
liquid level warns will be initiated. This
value is always detecting. The delay value
(default: 5s) and return value (default: 15)
also can be set.
Flexible Sensor 1
1
Flexible Sensor 1
Setting
(0~1)
0
0: Disable 1: Enable; (can be set as
temperature/pressure/fuel level sensor).
Flexible Sensor 2
1
Flexible Sensor 2
Setting
(0~1)
0
0: Disable; 1: Enable; (can be set as
temperature/pressure/fuel level sensor).
Digital Input Ports
Digital Input Port 1
1
Contents Setting
(0~55)
31
Remote start (demand).
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Digital Input Port 2
1
Contents Setting
(0~55)
27
Low oil pressure shutdown
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Digital Input Port 3
1
Contents Setting
(0~55)
26
High temperature shutdown
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Digital Input Port 4
1
Contents Setting
(0~55)
13
Gen Closed.
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Digital Input Port 5
1
Contents Setting
(0~55)
0
User defined.
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3
Active Range
(0~3)
3
0: From safety on 1: From starting 2:
Always active 3: Inactive
4
Active Actions
(0~4)
4
0: Warn; 1: Shutdown; 2: Trip and stop 3:
Trip 4: Indication
5
Delay
(0~20.0)s
2.0
Time from detecting input port is active to
confirm.
6
Description
LCD display detailed contents when the
input is active.
Digital Input Port 6
1
Contents Setting
(0~55)
44
First priority.
2
Active Type
(0~1)
0
0: Closed to active