HGM8151 Genset Parallel Controller User Manual Page 26 of 66
No.
Items
Parameters
Defaults
Description
Controller detects when it is ready to load.
It won’t switch on when speed is under
loading speed.
5
Loss
of
Speed
Signal
(0~3600)s
5
Time from detecting speed is 0 to confirm
the action.
6
Loss
of
Speed
Signal Action
(0~1)
0
0: Warn; 1:Shutdown
7
Over
Speed
Shutdown
(0~200)%
114
Setting value is percentage of rated speed
and delay value (over speed shutdown
default: 2s and under speed shutdown
default: 3s) also can be set.
8
Under
Speed
Shutdown
(0~200)%
80
9
Over Speed Warn
(0~200)%
110
Setting value is percentage of rated speed,
return value (over speed default: 108 and
under speed default: 90) and delay value
(default: 5s) also can be set.
10 Under Speed Warn
(0~200)%
86
11
Battery
Rated
Voltage
(0~60.0)V
24.0
Standard for detecting of over/under
voltage of battery.
12
Battery Over Volts
Alarm
(0~200)%
120
Setting value is percentage of rated voltage
of battery, delay value (default: 60s) and
return value (over voltage default: 115 and
under voltage default: 90) also can be set.
13
Battery Under Volts
Alarm
(0~200)%
85
14 Charge Alt Fail
(0~60.0)V
8.0
In normal running, when charger D+(WL)
voltage under this value, charge failure
alarms.
15 Start Attempts
(1~10) times
3
Max. Crank times of crank attempts. When
reach this number, controller will send start
failure signal.
16 Crank Disconnect
(0~6)
2
See table 16.
There are 3 conditions of disconnecting
starter with engine. Each condition can be
used alone and simultaneously to
separating the start motor and genset as
soon as possible.
17
Disconnect
Generator Freq
(0~200)%
30
Setting value is percentage of gen rated
frequency. When generator frequency
higher than the set value, starter will be
disconnected.
See
the
installation
instruction.
18
Disconnect Engine
Speed
(0~200)%
30
Setting value is percentage of rated speed.
When generator speed is higher than the
set value, starter will be disconnected. See
the installation instruction.
19 Disconnect
Oil (0~1000)kPa
200
When generator oil pressure higher than the