ACC7200 Air Compressor Controller User Manual Page 9 of 77
Items
Contents
Bump Test
25g, 16ms, self-sine
IEC 60255-21-2
Production Compliance
According to EN 61010-1 installation category (over voltage category)
III, 60V, pollution class 2, altitude 3000m
Case Dimensions
209mm x 166mm x 49mm
Panel Cutout
186mmx141mm
Working Temperature
(-30~+70)°C;
Working Humidity
(20~93)%
Storage Temperature
(-40~+80)°C
Protection Level
Front panel: IP65, when water proof gasket ring inserted between panel
and housing.
Back Panel: IP60
Insulation Intensity
Apply AC2.2kV voltage between high voltage terminal and low voltage
terminal and the leakage current is not more than 3mA within 1min.
Weight