ACC7200 Air Compressor Controller User Manual Page 29 of 77
No.
Item
Range
Default
Description
complete stop.
14
After Stop Time
(0-3600)s
0
Time from complete stop
to standby status.
15
Fuel Pre-supply Rest Time
(0-12)h
2
Interval time from this
pre-supply is completed to
next
pre-supply
is
outputted when output is
configured
to
fuel
pre-supply in standby state;
when it is set to 0,
pre-supply will not output
in standby state.
16
Fuel Pre-supply Time
(3-30)s
5
Time for pre-supply output
when output is configured
to fuel pre-supply.
Engine Setting
1
Engine Type
(0-39)
34
Default: 34: GTSC1.
2
Enable ECU Alarm Shut
(0-1)
1
0: Disable
1: Enable
NOTE
: When engine detects red
light alarm it will stop when it is
enabled.
3
Flywheel Teeth
(1.0-300.0)
118.0
Flywheel teeth of engine,
used for starter disconnect
conditions
and
engine
speed detection; please
refer
to
the
below
installation.
4
Engine Rated Speed
(0-6000)r/min
2200
Provide standard for over
speed, under speed and
load speed detection.
5
Engine Idle Set
(0-100.0)%
64.0
Rated speed percentage; if
idle running is needed, it
can make speed steady at
the set value.
6
Start Attempts
(1-10) Times
3
Maximum start times in
case of failed start; when
this number is reached,
controller shall issue Failed
to Start signal.
7
Crank Disconnect Connections
(0-2)
2
Please refer to Table 13.
There are two kinds of
disconnect conditions for
engine and starter. They
can be used independently