ACC7200 Air Compressor Controller User Manual Page 37 of 77
No.
Item
Range
Default
Description
the max. open time.
3
Screw Oil Cooler
Control 2
Enable
(0-1)
0
0: Disable; 1: Enable.
After enabled, when the
external
discharge
temperature sensor value
is higher than the open
value, cooler will output;
when it is lower than the
close value, cooler not
output.
When the max. open time
set as 0, output port works
according to the open and
close values, not limited by
the max. open time.
Open
(0-300)°C
80
Close
(0-300)°C
75
Max.
Open
Time
(0-3600)min
0
Digital Input Ports
Digital Input 1
1
Contents Setting
(0-53)
3
Alarm Reset; Please refer
to Table 12 for details.
2
Active Type
(0-1)
0
0: Active for Close
1: Active for Open
Digital Input 2
1
Contents Setting
(0-53)
26
High Temp. Shutdown
Input;
Please refer to Table 12 for
details.
2
Active Type
(0-1)
0
0: Active for Close
1: Active for Open
Digital Input 3
1
Contents Setting
(0-53)
27
Low
Oil
Pressure
Shutdown Input;
Please refer to Table 12 for
details.
2
Active Type
(0-1)
0
0: Active for Close
1: Active for Open
Digital Input 4
1
Contents Setting
(0-53)
0
Users defined;
Please refer to Table 12 for
details.
2
Active Type
(0-1)
0
0: Active for Close
1: Active for Open
3
Active Range
(0-3)
2
0: From Safety On
1: From Crank
2: Always
3: Inactive