ACC7200 Air Compressor Controller User Manual Page 72 of 77
14.11
MTU MDEC
Suitable for MTU engines, 2000 series, 4000 series. Engine type:
mtu-MDEC-303.
Table 31 X1 Connector
Terminals of controller
X1 connector
Remark
Auxiliary Output 1
BE1
AUX. Output 1 is configured as “29: Fuel
Relay Output” (The configuration is factory
default).
Auxiliary Output 2
BE9
AUX. Output 2 is configured as “28:
Starting Relay Output” (The configuration
is factory default).
-
E
Communication shielding line (connect
with one terminal only).
CAN(H)
G
Using impedance 120Ω connecting line.
CAN(L)
F
Using impedance 120Ω connecting line.
14.12
MTU ADEC (SMART MODULE)
Suitable for MTU engine with ADEC (ECU8) and SMART module. Engine type: mtu-ADEC.
Table 32 ADEC (X1 Port)
Terminals of controller
ADEC (X1 port)
Remark
Auxiliary Output 1
X1 10
AUX. Output 1 is configured as “29: Fuel
Relay Output” (The configuration is factory
default).
X1 Terminal 9 connected to negative of
battery.
Auxiliary Output 2
X1 34
AUX. Output 2 is configured as “28:
Starting Relay Output” (The configuration
is factory default).
X1 Terminal 33 connected to negative of
battery.
Table 33 ADEC (X4 Port)
Terminals of controller
SMART (X4 port)
Remark
-
X4 3
CAN communication shielding wire.
CAN(H)
X4 1
Using impedance 120Ω connecting line
CAN(L)
X4 2
Using impedance 120Ω connecting line.