ACC7200 Air Compressor Controller User Manual Page 28 of 77
No.
Item
Range
Default
Description
17
DPF Smoke and Dust Load Rate
( - )
18
SCR Inlet Temp
( - )
19
SCR Outlet Temp
( - )
Timer Setting
1
Start Delay
(0-3600)s
1
Time from remote start
signal
is
active
to
compressor is started.
2
Stop Delay
(0-3600)s
1
Time from remote start
signal
is
inactive
to
compressor is stopped.
3
Preheat Delay
(0-3600)s
0
Time for pre-heating plug
to be energized before
starter is energized.
4
Prestart Fuel Time
(0-3600)s
1
Time for fuel relay output
every time before starter is
energized.
5
Cranking Time
(3-60)s
8
Time for starter to be
energized every time.
6
Crank Rest Time
(3-60)s
10
Waiting
time
before
second energization when
engine fails to start.
7
Safety On Delay
(0-3600)s
10
During
this
time
oil
pressure low, temp. high,
under
speed,
under
frequency, under voltage,
and charge alt failure
alarms are all inactive.
8
Start Idle Time
(0-3600)s
10
Time for engine idle
running in start process.
9
Warming Up Time
(0-3600)s
0
Warming up time for
engine
before
normal
running after high speed
running.
10
Cooling Time
(0-3600)s
0
Cooling time before stop.
11
Stop Idle Time
(0-3600)s
10
Time for engine idle
running in stop process.
12
ETS Solenoid Hold
(0-3600)s
20
Time for ETS to be
energized before stop.
13
Wait Stop Time
(0-3600)s
0
Time after idle running
delay before complete stop
when “ETS Output Time” is
set 0; When “ETS Output
Time” is not 0, it is time
after ETS delay before