ACC7200 Air Compressor Controller User Manual Page 32 of 77
No.
Item
Range
Default
Description
maintain at the speed.
12
Over
Pressure
Auto Unload
Set
(0-200)%
120
Set value is compressor
target
pressure
percentage; return value
and delay value can also
be set.
Return
(0-200)%
110
Delay
(0-3600)s
5
13
Bypass
Valve
Control
Enable
(0-1)
0
0: Disable 1: Enable.
Bypass Speed (0-6000)r/min
1300
The set value is the engine
speed, the bypass pressure
is also available for setting.
Bypass
Pressure
(0-30000)kPa
300
14
Auto Onload Enable
(0-1)
0
0: Disable 1: Enable.
15
High
Discharge
Pressure Start
Inhibit
Enable
(0-1)
0
Discharge
Pressure
(0-1000)
50kpa
Start
inhibited
when
discharge
pressure
is
higher than this value.
Analog Sensor Setting
Engine Temperature Setting
1
Curve Type
(0-15)
9
SGD; see Table 13.
2
Open Action
(0-2)
0
0: Warning; 1: Shutdown;
2: None
3
Display Unit
(0-1)
0
0: °C; 1: °F
4
Over Shutdown
Enable
(0-1)
1
When temp. sensor value
is higher than this value,
controller issues temp.
over shutdown alarm; This
value is detected only after
safety on delay. Delay
value can be set.
Set
(0-300)
℃
98
Delay
(0-3600)s
3
5
Over Warn
Enable
(0-1)
1
When temp. sensor value
is
higer
this
value,
controller issues temp.
over shutdown alarm; This
value is detected only after
safety on delay. Return and
delay value can be set.
Set
(0-300)
℃
95
Return
(0-300)
℃
93
Delay
(0-3600)s
5
6
Under Warn
Enable
(0-1)
0
When temp. sensor value
is lower than this value,
controller issues temp. low
warning alarm; This value
is detected always. Delay
value and return value can
be set.
Set
(0-300)
℃
70
Return
(0-300)
℃
75
Delay
(0-3600)s
5
7
Onload Inhibit Under Temp.
(0-300)°C
30
When temp. sensor value
is lower than this value,