Initial Commissioning
SMA Solar Technology AG
56
SI5048-TEN093630
Technical Description
–
"New System"
(if you would like to start a new system or perform changes to the system
configuration)
–
"New Battery"
(if you wish to reset battery-specific parameters only. You cannot change
general parameters using "New Battery")
–
"Emerg Charge"
(if you would like to charge a deeply discharged battery using an
external source)
3. Use
"New System"
to set the following parameters:
– Device type (master, slave 1, slave 2, slave 3)
– Voltage/frequency type (230V_50Hz, 220V_60Hz), default setting is "230V_50Hz"
– System configuration (see table for setting options), preset to "1Phase1".
– date / time
– Battery type (VRLA, FLA, NiCd), default setting is "VRLA"
– Nominal voltage of the battery (42 V - 52 V in 2-V steps for FLA and VRLA, 43.2 V to 48 V
in 1.2-V steps for NiCd), default setting: "48.0 V"
– Nominal battery capacity (100 Ah - 10000 Ah), default setting: "100 Ah"
Systems with one Sunny Island
If only one Sunny Island is used in the system, the device type is set to "master" and is not
displayed.
Displayed text
Description
3Phase
Three-phase system, 3 Sunny Islands
1Phase1
Single-phase system, 1 Sunny Islands
1Phase2
Single-phase system, 2 Sunny Islands
1Phase3
Single-phase system, 3 Sunny Islands
1Phase4
Single-phase system, 4 Sunny Islands
MC-Box
Setting for multicluster operation
Battery types
VRLA
:
V
alve
R
egulated
L
ead
A
cid
Closed lead acid batteries with immobilized electrolyte in gel or AGM (
A
bsorbent
G
lass
M
at Separator) in all standard designs available on the market (grid plate, tubular plate,
small, large, AGM, Gel, etc.)
FLA
:
F
looded
L
ead
A
cid
Closed lead acid batteries with liquid electrolyte in all standard designs available on the
market (grid plate, tubular plate, small, large, etc.)
NiCd
:
Ni
ckel-
C
a
d
mium
Pocket-type plate or fiber plate closed nickel cadmium batteries
Содержание SI 5048
Страница 1: ...SI5048 TEN093630 TBE SI5048 Version 3 0 EN Off grid Inverter SUNNY ISLAND 5048 Technical Description...
Страница 2: ......
Страница 10: ...Table of Contents SMA Solar Technology AG 10 SI5048 TEN093630 Technical Description...
Страница 43: ...SMA Solar Technology AG Electrical Connection Technical Description SI5048 TEN093630 43...
Страница 66: ...Operation SMA Solar Technology AG 66 SI5048 TEN093630 Technical Description Overview of the menu structure...
Страница 209: ......
Страница 210: ......
Страница 212: ...4 4PMBS 5FDIOPMPHZ XXX 4 EF...