Electrical Connection
SMA Solar Technology AG
34
SI5048-TEN093630
Technical Description
Install the DC connections in the following sequence:
1. Loosen the cable screw connection on the Sunny Island.
2. Thread the DC cable through the cable screw connection.
3. Remove the protective insulation from the conductor and fit a suitable ring cable lug to the
exposed end of the conductor.
4. Install the M32 cable screw connection (included in delivery) for "DC−" and "DC +" in the cable
feed-throughs.
– Introduce the cable screw connection with the thread in the cable feed-through.
– Screw the counter-nut onto the cable screw connection thread on the inside of the housing
and tighten.
5. Attach the "DC−" cable with the ring cable lug to the "DC−" connection terminal and tighten the
screw with a torque of 4 to 5.7 Nm.
6. Attach the "DC+" cable with the ring cable lug to the "DC+" connection terminal and tighten the
screw with a torque of 4 to 5.7 Nm.
DC- connection area
The areas between the ring cable lug and the connection area must be clean. This way a
transition resistance is avoided and the heating of the terminals is reduced.
DC cables
Do not connect any other components to the DC cables. Other components must be
connected directly to the battery via separate cables.
Содержание SI 5048
Страница 1: ...SI5048 TEN093630 TBE SI5048 Version 3 0 EN Off grid Inverter SUNNY ISLAND 5048 Technical Description...
Страница 2: ......
Страница 10: ...Table of Contents SMA Solar Technology AG 10 SI5048 TEN093630 Technical Description...
Страница 43: ...SMA Solar Technology AG Electrical Connection Technical Description SI5048 TEN093630 43...
Страница 66: ...Operation SMA Solar Technology AG 66 SI5048 TEN093630 Technical Description Overview of the menu structure...
Страница 209: ......
Страница 210: ......
Страница 212: ...4 4PMBS 5FDIOPMPHZ XXX 4 EF...