Connecting External Sources
SMA Solar Technology AG
122
SI5048-TEN093630
Technical Description
The standard solution in such cases is to use a transfer switch that can be purchased as a manual or
an automatic switch. By using such a switch, a diesel generator is connected to the AC2 connection,
to which the public grid is normally connected, as displayed in the figure below:
To use such a switch, proceed with the installation as follows:
1. Connect the negative pole of the DigIn connection on the Sunny Island to the negative pole of
the BatVtgOut connection, also located on the Sunny Island.
2. Connect the positive pole of the DigIn connection to a NO connection of an auxiliary contact
of the transfer switch.
3. Connect the positive pole of the BatVtgOut connection to the second contact of the same
auxiliary contact on the transfer switch.
An auxiliary contact is used because the Sunny Island must “know” whether it is connected to the
public grid or whether it must manage a diesel generator.
To enable such a kind of operation, you must set the "231.06 ExtSrc" parameter to "GenGrid"
(see chapter 8.2 ”Starting the Quick Configuration Guide (QCG)” (page 55)).
Settings Performed on the Generator and Grid
All the settings made for the generator and grid in the submenus also apply to the
“GenGrid” selection.
Содержание SI 5048
Страница 1: ...SI5048 TEN093630 TBE SI5048 Version 3 0 EN Off grid Inverter SUNNY ISLAND 5048 Technical Description...
Страница 2: ......
Страница 10: ...Table of Contents SMA Solar Technology AG 10 SI5048 TEN093630 Technical Description...
Страница 43: ...SMA Solar Technology AG Electrical Connection Technical Description SI5048 TEN093630 43...
Страница 66: ...Operation SMA Solar Technology AG 66 SI5048 TEN093630 Technical Description Overview of the menu structure...
Страница 209: ......
Страница 210: ......
Страница 212: ...4 4PMBS 5FDIOPMPHZ XXX 4 EF...