TROUBLESHOOTING, STATUS LIGHT
TROUBLESHOOTING, ROCKER SWITCH
26
LED CODE
SYSTEM DESCRIPTION
ACTIONS
Steady On
Normal
LED is on.
1.
24 VAC is applied to the control.
LED Off
Lockout
LED is off .
1.
Check 120 volt is supplied to unit and transformer.
2.
Check to see if 24 volt is coming out of secondary side of
transformer; if not, change transformer.
3.
Set thermostat SP above room temperature.
4.
Check to see if 24 volt is supplied to and returned from
thermostat.
1 Flash
Lockout
Air pressure switch contacts are
closed before blower motor starts
1.
Check pressure hose connection between the blower
motor and pressure switch.
2.
Replace pressure switch
2 Flashes
Lockout
Pressure switch stuck open when
blower motor is ON.
Fresh air modular cable disconnect
1.
Check wiring between PS1 and PS2 on the ignition con-
trols for proper connection.
2.
Check pressure switch function.
3.
If pressure switch contracts remain opened, replace pres-
sure switch.
4.
Check fresh air modular cable connections between the
fresh air modular and the heater.
5.
Check cable for cuts or damages.
3 Flashes
Lockout
Ignition lockout from too many trials.
1.
Verify that gas supply available.
2.
Verify that the gas valve is receiving 24 VAC.
3.
Check if spark igniter is cracked or dirty.
4.
Check ground circuit wiring.
5.
Check the high limit switch, reset if needed.
4 Flashes
Lockout
Ignition lockout from too many flame
losses within a single call for heat.
1.
Check pressure switch hose for leaks or poor connection.
2.
Check pressure switch hose for condensate in line.
3.
Check grounding circuits.
4.
Check for cracked or dirty flame sensor.
5 Flashes
Lockout
Control hardware fault detected.
1.
Reset power supply to l ignition control board.
2. If
aft er resetting power supply and the 5 flashes still occur,
replace control board.
LED LIGHT
STATUS
CAUSE OF FAILURE
REMEDY
Power light
OFF
No voltage from outlet
Correct power supply
Ciruit breaker tripped
Reset breaker
High Limit Light
ON
High limit tripped
Reset high limit
CO light
OFF
CO above 100 ppm
Check for gas leaks, provide
proper ventilation
Содержание Sleeptight 800
Страница 16: ...SYSTEM COMPONENTS LP Gas Hose Assembly Fresh Air Fan Module 2 way LP Tank Manifold 15 Interconnect Cable ...
Страница 17: ...16 GAS TRAIN COMPONENTS ITEM DESCRIPTION 3 GAS CONTROL VALVE 4 CSST TUBE 5 IGNITER CABLE 6 IGNITER 3 4 5 6 ...
Страница 36: ...35 FRESH AIR MODULE WIRING DIAGRAM ...
Страница 41: ...Sisu Commercial Products LLC 5801 E 41st St Suite 1005 Tulsa OK 74135 www sisu ee com ...