d. Slowly open all the gas supply manual valve(s) and allow pressure to equalize.
e. Check all pipe connections, hose connections, manual valves, fittings, and adapters upstream
of the heater’s electronic gas control valve for gas leaks using approved gas leak detectors. In
the event a gas leak is detected, check the components involved for cleanliness and further
tighten as necessary to stop the leak. Do not proceed until all leaks are eliminated.
Heater Gas Hose Connection
WARNING:
Use pipe thread compound at all gas connection. All gas leaks detected
must be repaired before heater is placed into service.
1. Attach the male quick connector to the ridged part of the hose.
2. Install the street elbow to the gas valve inlet.
3. Install the hose adapter to the street elbow.
4. Attach the hose to the hose adapter.
Electrical Connection
a. Plug the Interconnect Cable into the fresh air fan module and the heater.
b. Plug the electrical power cord into the Fresh Air Fan Module and Heater. Plug both into a
properly grounded 115V 60Hz outlet (15A or greater).
WARNING:
This appliance is equipped with a three-prong (grounding) plug for your
protection against shock hazard and should be plugged directly into a properly grounded
three-prong receptacle.
22
Quick Connector
Street Elbow
Hose Adapter
Содержание Sleeptight 800
Страница 16: ...SYSTEM COMPONENTS LP Gas Hose Assembly Fresh Air Fan Module 2 way LP Tank Manifold 15 Interconnect Cable ...
Страница 17: ...16 GAS TRAIN COMPONENTS ITEM DESCRIPTION 3 GAS CONTROL VALVE 4 CSST TUBE 5 IGNITER CABLE 6 IGNITER 3 4 5 6 ...
Страница 36: ...35 FRESH AIR MODULE WIRING DIAGRAM ...
Страница 41: ...Sisu Commercial Products LLC 5801 E 41st St Suite 1005 Tulsa OK 74135 www sisu ee com ...