5.
Technical data
5.1. General
Secos energy saving controller
Number of connectable room thermostats
Up to 8
Number of operable heating circuits per control zone
1 - 14 heating circuits
Dimensions H x W x D
328 x 97 x 61 mm
Protection code
IP 20
Permissible ambient conditions
-10 - 60 °C, max. relative humidity 80 %, air pressure 750 - 1050 hPa
Supply voltage
230V AC / 50-60 Hz
Power consumption
max. 500 W
Output voltage for circulating pump
230V AC / 50-60 Hz
Interface for building management system
Modbus RTU
Frequency range for wireless connection
2402 - 2484 MHz
Maximum transmitting power
5 dBm
Secos system manifolds
Number of heating circuits
4 - 14 heating circuits
Dimensions
(See Dimensions table)
Max. operating temperature:
75 °C
Max. operating pressure:
10 bar
Volume flow per heating circuit
0 - 8 l/min
Operating medium:
Heating water according to VDI 2035
Pressure loss system manifold complete
kvs 1.19 m³/h
Primary connections
G1" F
Secondary connections
G3/4" M Eurocone
Material of manifold bar
Stainless steel
Material of valves
ceramic disc valves
Secos supply line temperature sensor
Ø 6 x 50 mm
Closing stroke ceramic valve
90°
Secos actuator
Dimensions H x W x D
47 x 77 x 57 mm
Operating temperature
-10 to 60 °C
Protection code
IP 20
Secos multisensor
Measuring range for flow rate
0 - 8 l/min
Measuring range for temperature
+10 to +75 °C
Sensor characteristics
Temperature
10 °C
15 °C
20 °C
25 °C
30 °C
35 °C
40 °C
45 °C
50 °C
55 °C
60 °C
65 °C
70 °C
75 °C
Multisensor [Ω]
52.0
52.9
53.9
54.9
55.8
56.8
57.8
58.7
59.7
60.7
61.6
62.6
63.5
64.5
Temperature sensor
for supply line [Ω]
1039
1058
1078
1097
1117
1136
1155
1175
1194
1213
1232
1251
1271
1290
Secos
- Simplex Energy Control System
Installation instructions
|
Operating instructions