8.7. Connecting room thermostats
Improper electrical connection may result in danger to life through electric shock.
X
Electrical connection should only be carried out by an electrician approved by the local power supply company
and in accordance with the locally applicable regulations.
X
Disconnect the supply voltage before working.
X
Do not open the housing parts!
Up to 8 room thermostats can be connected to the energy saving
controller. If a room thermostat is used as master, it must be con-
nected to terminal location 8.
The remaining terminal locations 1 - 7 can be used as required. All
heating circuits are assigned to the room thermostats in the app.
Both 2-point room thermostats and room thermostats with
PWM characteristic can be connected and utilised.
Only 230V room thermostats may be connected.
23
Connecting room thermostats
24
Connection of Master / Slave room thermostats
N
out-timer
Slave
T
N
L
T
Master
L
in-timer
L1-7 N1-7
Set-back operation for room thermostats
Thermostat with set-back output is connected to terminal block 8. Thermostats with set-back input use this signal via the respective
connection, terminal blocks 1 to 7.