User manual - DATA RECORDER SRD-99 and cooperating software
Register Write
Range
Register description
38h
No
Written memory in kB
39h
No
Approximated time remaining until memory is filled with recorded
measurement results – Higher (2
nd
) byte (parameter in seconds).
3Ah
No
Approximated time remaining until memory is filled with recorded
measurement results – Lower (1
st
) byte (parameter in seconds).
Configuration parameters for channel No. 1 (
I version
)
40h
Yes
0÷2
“
Input type
” parameter in “
Inputs settings
” submenu for channel 1:
0
- inactive;
1
- 0-20mA;
2
- 4-20mA
41h
Yes
-9999÷9999 “
Lo value
” parameter in “
Inputs settings
” submenu for channel 1
(not considering decimal point)
42h
Yes
-9999÷9999 “
Hi value
” parameter in “
Inputs settings
” submenu for channel 1 (not
considering decimal point)
43h
Yes
0÷3
“
Dec. point
” parameter in “
Inputs settings
” submenu for
channel1:
0
- 0;
1
- 0,0;
2
- 0,00;
3
- 0,000
44h
Yes
0÷5
“
Filter
” parameter in “
Inputs settings
” submenu for channel 1:
(filtration coefficient)
45h
Yes
0÷399
“
Lower ext.
” parameter in “
Inputs settings
” submenu for channel 1
expressed in 0.01 mA (not considering decimal point)
46h
Yes
0÷199
“
Upper ext.
” parameter in “
Inputs settings
” submenu for channel 1
expressed in 0.01 mA (not considering decimal point)
Configuration parameters for channel No. 1 (
RTD version
)
40h
Yes
0÷2
“
Input type
” parameter in “
Inputs settings
” submenu for channel 1:
0
- inactive;
1
- PT100;
2
- PT500
3
- PT1000
41h
Yes
-9999÷9999
“
Lo value
” parameter in “
Inputs settings
” submenu for channel 1
expressed by 0,1°C or °F
(not considering decimal point)
42h
Yes
-9999÷9999
“
Hi value
” parameter in “
Inputs settings
” submenu for channel 1
expressed by 0,1°C or °F
(not considering decimal point)
43h
No
1
“
Dec. point
” parameter in “
Inputs settings
” submenu for
channel1, constant value:
1
- 0,0
44h
Yes
0÷5
“
Filter
” parameter in “
Inputs settings
” submenu for channel 1:
(filtration coefficient)
45h
Yes
-99÷99
“
Bias
” parameter in “
Inputs settings
” submenu for channel 1
expressed
by 0,1°C
or °F
(
shift of measurement scale
)
Configuration parameters for channel No. 1 (common)
47h
Yes
Character
“
Name
” parameter in “
Inputs settings
” submenu for channel 1;
Higher byte – character No. 1; Lower byte – character No. 2
48h
Yes
Character
“
Name
” parameter in “
Inputs settings
” submenu for channel 1;
Higher byte – character No. 3; Lower byte – character No. 4
49h
Yes
Character
“
Name
” parameter in “
Inputs settings
” submenu for channel 1;
Higher byte – character No. 5; Lower byte – character No. 6