DIAS-DRIVE 335-23
Page 40
27.09.2017
3.5.2
Classic Emergency Stop Functions (Stop Category 0)
The cable length for the motor is limited to 25 m. If a longer cable is used, additional
suppression coils in the motor output are required.
Note:
The K
EM
coil must be turned on before the amplifier is enabled and
can be turned off after at least 1 ms after the amplifier is disabled.
The resistance value and the power of the R
EM
resistor are calculated using the following
formulas:
maxSPEED
maximum revolutions [rpm]
I
max
maximum motor current allowed [A]
K
Erms
voltage constant of the motor [V*min]
8
.
0
max
max
I
K
SPEED
R
Erms
EM
10
)²
8
.
0
(
max
EM
EM
R
I
W
P