DIAS-DRIVE 335-23
Page 30
27.09.2017
2.2.6
External Fusing
The AC-mains and 24 V fuses are designed according to the customer requirements for the
circuit.
Signal
Fuses, time delay
AC mains input (L1-L3)
Suitable for use on a circuit
capable of delivering not more than
5000 rms symmetrical amperes,
528 volts maximum when
protected by RK5 class fuses rated
20 A
The size of the fuse depends on the average power consumption
of the connected amplifier. Max. 20 A with 4 mm²
(12 AWG) (FRS-25) wires
24 V DC input (24 V, 24 V-BR to
BGnd)
16 A slow-blow at 2.5 mm² (14 AWG) for the control
External regen resistor
10 A time delayed, 1200 V (e.g. SIBA 10 022 01,
3-pin-D-Fuse-Link) or FRS-10