4-20 mA Output Wiring
All InnovaMass 240i/241i Series flow meters are equipped with calibrated 4-20 mA output
signals for flow, temperature, and pressure.
The 4-20 mA current loop output is non-isolated. Max load 500 ohms.
Figure 13. 4-20mA Output Connections
Figure 14. Ferrite Installation (Ferrite not required for conduit)
Alarm Output Wiring
One alarm output contact is included on the flow meter terminal block. The alarm output is
driven by an optical relay that is normally-open single-pole. The relay is isolated and
requires a separate power supply (isolated). The voltage of the alarm output is the same as the
voltage supplied to the circuit.
To use an external power supply for an isolated alarm output, connect as shown in Figure 15.
You may set low, high or window alarms for temperature, pressure, totalizer, mass flow or
volumetric flow
.
Do not externally power the 4-20mA output loop. It is a self-powered
loop.