6 – 14
2)
Only permissible if the power circuit may be interrupted!
Fixed-moun-
ted breaker
Draw-out
breaker
Disturbance
Possible Cause(s)
Remedy
X
X
Circuit breaker cannot be
closed.
Circuit breaker ready to close.
Ready-to-close indicator:
1.
Closing coil not energized or
incorrectly energized
Check or apply correct voltage
X
2.
Circuit breaker in disconnected
position in guide frame
Rack circuit breaker into test or con-
nected position
X
3.
The secondary disconnects have
been removed
Plug in the secondary disconnects
X
Circuit breaker cannot be
moved from the maintenance
position into the disconnected
position
1.
Racking mechanism of circuit
breaker not in disconnected (DIS-
CON) position (Check circuit
breaker position indicator)
Rack the mechanism into discon-
nected position (green position indica-
tor)
X
Circuit breaker cannot be fit-
ted in the guide rails
1.
Factory mounted coding of circuit
breaker and guide frame doesn’t
match
Use circuit breaker type according to
guide frame label
X
When racking from the discon-
nected into the test position,
the circuit breaker does not
move during the first 6 turns
(approximately)
1.
Not a fault (functional property)
Rack further
X
Racking handle cannot be
drawn out
1.
Circuit breaker is closed
Press "OPEN" button and pull racking
handle block out
2)
X
2.
Cubicle door not completely
closed
(Locking device as accessory)
Close cubicle door
X
Racking handle cannot be
pushed in
1.
Racking handle is interlocked
Rack circuit breaker into discon-
nected, test or connect position,
unlatch crank and push crank fully in
X
Cubicle door cannot be
opened (door interlock as
accessory)
1.
Closed circuit breaker is prevent-
ing opening of cubicle door
Open the circuit breaker
2)
X
2.
Circuit breaker in connected posi-
tion
Rack circuit breaker into test or dis-
connected position
2)
Содержание WL Series
Страница 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Страница 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Страница 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Страница 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Страница 69: ...7 7 C class always 0494 5_nu top view rear view ...
Страница 70: ...7 8 0738_nu LH side view front view ...
Страница 71: ...7 9 7 3 Baugröße III Festeinbau 0495 1_nu LH side view 7 3 Frame size III fixed mounted version ...
Страница 72: ...7 10 0495 2_nu top view top view ...
Страница 73: ...7 11 0495 3_nu top view rear view ...
Страница 74: ...7 12 0739_nu LH side view front view ...
Страница 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Страница 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Страница 78: ...7 16 0746_nu rear view top view ...
Страница 79: ...7 17 0747_nu bottom view ...
Страница 80: ...7 18 0748_nu ...
Страница 81: ...7 19 0749_nu ...
Страница 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Страница 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Страница 87: ...7 25 ...
Страница 88: ...7 26 ...
Страница 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Страница 289: ...17 4 1 Selbstschneidende Schraube 2 Bowdenzug 3 1 PZ 3 5 Nm 2 2 3 5 6 1 Self tapping screw 2 Bowden wire 4 9 7 8 ...
Страница 360: ......
Страница 361: ......