25 – 1
25
Technische Daten
WL Circuit Breakers UL 489
Breaker Ratings
1) Available in 2006
2) Definition: With Trip unit setting L & S set to max and I = OFF, close and latch ratings are the maximum current (less than or equal to I
CW
) the breaker can close into
and remain closed until tripped by the full 30 cycle short-time band (0.5 s).
A WL Circuit Breaker will close & latch up to the max. Interrupting Current I
CU
. Above I
CW
the tripping will occur after 30 ms.
Frame Size I
Frame Size II
Frame Rating
800
1200
800
1200
1600
Rating Class
S
H
L
S
H
L
S
L
C
1)
S
L
C
1)
S
L
C
1)
Interrupting Current I
CU
(kAIR RMS) 50/60 Hz
240VAC
65
85
100
65
85
100
65
100
150
65
100
150
65
100
150
480VAC
65
85
100
65
85
100
65
100
150
65
100
150
65
100
150
600VAC
65
65
65
65
65
65
65
85
100
65
85
100
65
85
100
Short-time Withstand
Current I
CW
(kA RMS)
50/60 Hz
0.5 s
65
65
65
65
65
65
65
85
100
65
85
100
65
85
100
Extended Instantaneous
Protection (kA RMS -0% to
+20%)
240-480VAC
65
85
100
65
85
100
65
100
150
65
100
150
65
100
150
600VAC
65
65
65
65
65
65
65
85
100
65
85
100
65
85
100
Close and Latch Ratings
2)
(kA RMS) 50/60 Hz
65
65
65
65
65
65
65
85
100
65
85
100
65
85
100
Rating Plug Range (A)
200 to 800
200 to 1200
200 to 800
200 to 1200
200 to 1600
Minimum switchboard
cubicle dimensions
(fixed or draw-out version)
width (in.)
height (in)
depth (in)
22.0
15.0
19.5
22.0
22.5
19.5
Frame Size II
Frame Size III
Frame Rating
2000
2500
3000
4000
5000
Rating Class
S
L
C
1)
L
C
1)
L
C
1)
L
C
L
C
Interrupting Current I
CU
(kA RMS) 50/60 Hz
240VAC
65
100
150
100
150
100
150
100
150
100
150
480VAC
65
100
150
100
150
100
150
100
150
100
150
600VAC
65
85
100
85
100
85
100
85
100
85
100
Short-time Withstand
Current I
CW
(kA RMS)
50/60 Hz
0.5 s
65
85
100
85
100
85
100
85
100
85
100
Extended Instantaneous
Protection (kA RMS -0% to
+20%)
240-480VAC
65
100
150
100
150
100
150
100
150
100
150
600VAC
65
85
100
85
100
85
100
85
100
85
100
Close and Latch Ratings
2)
(kA RMS) 50/60 Hz
65
85
100
85
100
85
100
85
100
85
100
Rating Plug Range (A)
200 to 2000
200 to 2500
200 to 3000
800 to 4000
800 to 5000
Minimum switchboard
cubicle dimensions
(fixed or draw-out version)
width (in.)
height (in)
depth (in)
22.0
22.5
19.5
32.0
22.5
19.5
32.0
30.0
19.5
32.0
22.5
19.5
32.0
30.0
19.5
25
Technical Data
Содержание WL Series
Страница 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Страница 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Страница 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Страница 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Страница 69: ...7 7 C class always 0494 5_nu top view rear view ...
Страница 70: ...7 8 0738_nu LH side view front view ...
Страница 71: ...7 9 7 3 Baugröße III Festeinbau 0495 1_nu LH side view 7 3 Frame size III fixed mounted version ...
Страница 72: ...7 10 0495 2_nu top view top view ...
Страница 73: ...7 11 0495 3_nu top view rear view ...
Страница 74: ...7 12 0739_nu LH side view front view ...
Страница 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Страница 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Страница 78: ...7 16 0746_nu rear view top view ...
Страница 79: ...7 17 0747_nu bottom view ...
Страница 80: ...7 18 0748_nu ...
Страница 81: ...7 19 0749_nu ...
Страница 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Страница 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Страница 87: ...7 25 ...
Страница 88: ...7 26 ...
Страница 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Страница 289: ...17 4 1 Selbstschneidende Schraube 2 Bowdenzug 3 1 PZ 3 5 Nm 2 2 3 5 6 1 Self tapping screw 2 Bowden wire 4 9 7 8 ...
Страница 360: ......
Страница 361: ......