9 – 67
9.1.11
Rating plug
The rating plug defines the rated continuous current I
n
.
If a rating plug with a higher current than the maximum permissible
circuit breaker rated continuous current is plugged in, the electronic
system of the trip unit recognizes this error and signals it with a
flashing T.U. ERROR indicator.
The trip unit ignores the default value for the rated continuous cur-
rent provided by the false rating plug and adjusts it to the value of
the smallest rating plug provided for the frame size of the circuit
breaker concerned.
The same happens if a circuit breaker with frame size III is equipped
with a rating plug smaller than 800 A or no rating plug is fitted at all.
All set protection parameters are adjusted accordingly.
If a circuit breaker is started up without a rating plug, the
T.U. ERROR indicator will light up and the trip unit will trip.
9.1.11
Bemessungsstrommodul
Das Bemessungsstrommodul bestimmt den Bemessungsstrom I
n
innerhalb eines gewissen Bereiches für eine gegebene Baugröße
des Leistungsschalters.
Wird ein Bemessungsstrommodul für einen Strom gesteckt, der
größer ist, als der maximal zulässige Bemessungsstrom des Lei-
stungsschalters, so wird dieser Fehler von der Elektronik des Über-
stromauslösers erkannt und mit einer blinkenden Anzeige
T.U. ERROR signalisiert.
Der Überstromauslöser ignoriert den vom falschen Bemessungs-
strommodul vorgegebenen Wert für den Bemessungsstrom und
setzt diesen auf den Wert des für die Baugröße des betreffenden
Leistungsschalters kleinsten Bemessungsstrommoduls.
Gleiches passiert, wenn für einen Schalter der Baugröße III ein
Bemessungsstrommodul kleiner 800 A verwendet wird. Alle einge-
stellten Schutzparameter werden entsprechend angepasst.
Wird ein Leistungsschalter ohne Bemessungsstrommodul in
Betrieb genommen, leuchtet die Anzeige T.U. ERROR und der
Überstromauslöser löst aus.
Frame size
Baugröße
Rating plug
Bemessungstrom-modul
Catalog No.
Bestell-Nr.
I
II
III
200 A
WLRP200
225 A
WLRP225
250 A
WLRP250
300 A
WLRP300
315 A
WLRP315
350 A
WLRP350
400 A
WLRP400
450 A
WLRP450
500 A
WLRP500
600 A
WLRP600
630 A
WLRP630
700 A
WLRP700
800 A
WLRP800
1000 A
WLRP1000
1200 A
WLRP1200
1250 A
WLRP1250
1600 A
WLRP1600
Содержание WL Series
Страница 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Страница 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Страница 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Страница 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Страница 69: ...7 7 C class always 0494 5_nu top view rear view ...
Страница 70: ...7 8 0738_nu LH side view front view ...
Страница 71: ...7 9 7 3 Baugröße III Festeinbau 0495 1_nu LH side view 7 3 Frame size III fixed mounted version ...
Страница 72: ...7 10 0495 2_nu top view top view ...
Страница 73: ...7 11 0495 3_nu top view rear view ...
Страница 74: ...7 12 0739_nu LH side view front view ...
Страница 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Страница 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Страница 78: ...7 16 0746_nu rear view top view ...
Страница 79: ...7 17 0747_nu bottom view ...
Страница 80: ...7 18 0748_nu ...
Страница 81: ...7 19 0749_nu ...
Страница 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Страница 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Страница 87: ...7 25 ...
Страница 88: ...7 26 ...
Страница 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Страница 289: ...17 4 1 Selbstschneidende Schraube 2 Bowdenzug 3 1 PZ 3 5 Nm 2 2 3 5 6 1 Self tapping screw 2 Bowden wire 4 9 7 8 ...
Страница 360: ......
Страница 361: ......