43/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
New plant
22.06.2012
3.2.4 Refresh device list
Refresh data of the central communication unit’s device list and submit the data to the
ACS device list.
You must manually refresh the data if you changed device assignments, e.g. replaced
a defective device by a new device with same bus address but new serial number.
A plant with "central communication unit type OZW775" exists.
1.
Select
Plant > Refresh device
list
.
2.
Select
Refresh device
list
to start refreshing the list.
Refresh the device list: The KNX address or KNX serial number changed for one (or
several) device(s) in the "List of assigned devices".
Plant > Edit device
list…
is selected.
1. Select the symbol
in the menu tree.
2. Right-click to open the context menu and select
Refresh device list
to start refresh.
Function
Prerequisite
Workflow
2nd variant
Prerequisite
Workflow