Recommended commissioning
22.06.2012
Step
Section
Description
11
4.5
Refresh OZW775 reference data points
You must refresh the reference data points after the central communication unit
OZW775 is fully parameterized.
Prerequisite: Parameter set download completed.
Workflow:
1. Close all open applications and select
Plant > Edit device
list…
.
2. Select the row with symbol
in the right window pane and right-click to
open the context menu.
3. Select
Refresh reference
data points
to start refreshing.
Notes:
−
You can select several devices in the "List of assigned devices" to also refresh the
reference data points for several or all devices.
−
See Section 3.2.5 on "Refresh reference data points of devices.
12
4.6
Application [ Popcard ] "Commissioning mode = On"
Note:
−
Application [ Popcard ] "Commissioning mode = On" allows you to check the inputs
and outputs via data point "Wiring test active".
4.6.1
Data points in the "Commissioning" operating page
Command sequence:
Data points
Commissioning
Commissioning
mode
> Wiring test
Wiring test active
13
4.7
Application [ Popcard ] "Commissioning mode = Off"
Normal operation
Note:
−
"…" indicates the at the operating page displays data points described previously in
application [ Parameter setting ]; see Step 9.
4.7.1
Data points in the "Faults current" operating page
Command sequence:
Data points
Faults current
> Local
…
Acknowledge faults (write)
> System
> Most severe bus fault
Device name
(read-only)
Fault
information
(read-only)
Fault
text
(read-only)
Area
(read-only)
Line
(read-only)
Device
address
(read-only)
Device
type
(read-only)
Fault message will be deliv. (r-o)
> Fault 1…10
same as Most severe bus fault
but
without
Fault message will be delivered
4.7.2
Data points in the "Settings" operating page
Command sequence:
Data points
Settings
> Central communication unit
…
Reset admin password
> Communication
> Modem
…
Test message receiver
Time to next message
> Message receiver
Test message receiver
System report sent (read)
> System report
…
Next
report
> Faults
Delete history
>
Texts
…
Reset
text