37/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
New plant
22.06.2012
The code number (data point "code") corresponds to the plant’s access code.
The factory setting for the code number is "01". Do not change the code number
upon the initial connection with a central communication unit.
You can retroactively change the code number in this field if it is redefined during
central communication unit parameterization.
See Section 4.3.2, command sequence: Settings > Central comm unit.
Keep the USB port for the connection during commissioning and parameterization.
Click
Finish
to finish the entries.
6. Click
Yes
to refresh the device list.
The ACS reads the device list from the central communication unit and refreshes
the reference data points of the devices on "Yes".
7.
Select
Applications > Popcard…
to open the
[Popcard]
.
Note: After a connection is opened:
−
Symbol
(= connect) becomes inactive and
(= disconnect) becomes
active.
−
The application changes to
ACS Operating - [State – Connected]
.