Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Recommended commissioning
22.06.2012
Step
Section
Description
13
(continued)
4.7
Application [ Popcard ] "Commissioning mode = Off"
Normal operation
4.7.3
Data points in the "Device information" operating page
Command sequence:
Data points
Device information
> Central communication unit
…
Central comm unit type
Software version (firmware)
Hardware
version
> Konnex
…
Number of devices max
Number of devices min
Last
change
4.7.4
Data point "Time of day/date"
Data point "Time of day/date" is displayed multiple times and can be set in the
following applications:
[ Popcard ] "Commissioning mode = Off" Operating page "Commissioning"
[ Popcard ] "Commissioning mode = Off" Operating page "Time / Date"
[ Popcard ] "Commissioning mode = On" Operating page "Commissioning"
Set current data and time; see Section 5.4.1.
14
5.1
Tests following parameterization
5.1.1
Commissioning mode "On / Off"
−
"Commissioning mode = On" must be set to prevent events from being triggered
during testing (no state changes in the plants).
−
After you complete the wiring and communication tests, you must reset to
"Commissioning mode = Off"
prior to starting normal mode
.
15
5.2
Wiring test
5.2.1
Wiring test active "Yes / No"
−
"Wiring test active = Yes" must be set to be able to test the wiring at the inputs and
outputs.
−
Set again "Wiring test active = No" after you finish the wiring tests.
5.2.2
Wiring test for inputs
−
You can test inputs N.X1…N.X8 and N.D1…N.D8.
5.2.3
Wiring test for outputs
−
You can test outputs "Time switch 1…4" and "Fault relay 1…2".
16
5.3
Test message receiver
5.3.1
Communication to the message receiver
−
Test communication (possible with "Commissioning mode = On / Off");
see Section 5.3.1 for workflow.
5.3.2
Diagnose communication via modem
−
Test modem connection (possible with "Commissioning mode = On / Off");
see Section 5.3.2 for workflow.
5.3.3
Modem message interval
−
The time the central communication unit must wait between communication abortion
and reestablishing communication when connected via modem.
5.3.4
Error codes for modem communication