214/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
14 Communication
05.02.2007
Main menu > Commissioning > Communication > Distribution zones
Operating line
Range
Factory setting
Outside temperature zone
---- / 1…31
1
Solar zone
---- / 1…31
----
Wind zone
---- / 1…31
----
The settings made here are also displayed under:
Main menu > Device information > Communication > Distribution zones
When using setting “----“, the controller does not send the outside temperature signal
via bus.
Several outside temperature zones are possible:
•
Setting “Outside temperature zone“ in the communication settings of heating circuit 1
is identical with that under “Distribution zones“
•
Those of heating circuits 2 and 3 are set as follows:
Main menu > Commissioning > Communication > Heating circuit 2
(
or
3
)
Operating line
Range
Factory setting
Outside temperature zone
---- / 1…31
1
Every controller has one solar zone.
When using setting “----", the controller does
not
send the solar radiation signal via
bus.
Every controller has one wind zone.
When using setting “----“, the controller does
not
send the wind speed signal via bus.
14.7 Fault handling
Number Text
Effect
5000
No bus power supply
No bus power supply.
Nonurgent message; must not be ac-
knowledged
Number Text
Effect
5001
System time failure
Clock time master is missing or cannot be
received.
Nonurgent message; must not be ac-
knowledged
5002
>1 clock time master
There is more than one clock time master.
Nonurgent message; must be acknowl-
edged
5003
Invalid time of day
•
Time of day on the clock time master
must be readjusted
•
Reserve has elapsed
Nonurgent message; must not be ac-
knowledged
Number Text
Effect
5101
System time switch failure 1 Time switch master missing or cannot be
received.
Nonurgent message; must not be ac-
knowledged
Communication
Outside temperature zone
Solar zone
Wind zone
Faulty bus power supply
Time-of-day error
Failure of system
time switch