45/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
5 General functions, fundamentals
05.02.2007
Main menu > Commissioning > Communication > Heating circuit 1
(or
2
or
3
)
Operating line
Range
Factory setting
Geographical zone (apartm.)
---- / 1…126
----
Time switch slave (apartm.)
---- / 1…126
----
Main menu > Commissioning > Communication > DHW
Operating line
Range
Factory setting
DHW zone
1…31
1
Time switch operation
Autonomous / Slave /
Master
Autonomous
Time switch slave DHW
1…31
1
For details on settings regarding time switch communication, refer to chapter 14
”Communication“.
5.1.2 Entries
For space heating, a specific 24-hour program can be selected for each day:
Main menu > Heating circuit 1
(or
2
or
3
)
> Time switch 1
(or
2
or
3
)
Operating line
Range
Factory setting
Monday
Comfort / Precomfort /
Economy
From 06:00 Com-
fort / From 22:00
Economy
up to
Sunday
Comfort / Precomfort /
Economy
From 06:00 Com-
fort / From 22:00
Economy
Special day
Comfort / Precomfort /
Economy
From 06:00 Com-
fort / From 22:00
Economy
The times are to be entered with the help of a display (using indicator ):
Tuesday
From
Comfort
For DHW heating, a specific 24-hour program can be selected for each day:
Main menu > DHW > DHW time switch
Operating line
Range
Factory setting
Monday
Normal / Reduced
From 05:00 Nor-
mal
From 22:00 Re-
duced
up to
Sunday
Normal / Reduced
From 05:00 Nor-
mal
From 22:00 Re-
duced
Space heating
Note
DHW heating