38/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
3 Commissioning
05.02.2007
3.7
Device information
The
Device information
menu provides information about the controller, shows the soft-
ware version, etc.
Main menu > Device information > Controller
Operating line
Adjustable values / display / remarks
Plant type
Display of plant type
Plant type adapted
Display of intervention in the programmed
application (yes, no)
File name
Has a function only in connection with
ACS7… Display of file name of the applica-
tion currently loaded.
Can be edited under
Settings > Texts > File
name
.
Device type
RMH760B-1…RMH760B-5
Software version
Display of software version
Hardware version
Display of hardware version
Main menu > Device information > Position 1…4
Operating line
Adjustable values / display / remarks
Extension module
Display of the module’s type reference
Software version
Display of software version
Hardware version
Display of hardware version
3.8
Leaving the password level
On completion of commissioning, select the user level (access level for the plant opera-
tor). Proceed as follows:
1. After completing commissioning, you reach the “Main menu” again.
2. Press simultaneously the OK knob and the ESC button.
3. The
Access levels
menu appears.
4. Select the user level by turning the OK knob.
5. Confirm the selection by pressing the OK knob.
3.9
Marking an intervention
If the internal standard application has been adapted or if, subsequently, the “Extra
configuration” menu has been accessed, an asterisk (*) appears in front of the plant’s
type reference.
The asterisk denotes that the plant type has been complemented by extra functions.
The asterisk is set automatically when leaving the „Extra configuration” menu, even if
nothing has been changed. In addition, on the
Device information
menu,
Yes
will be set
on operating line
Plant type adapted
.
When, on the
Basic configuration
menu, the former or a new standard application is
loaded for the plant type, the asterisk disappears and
No
will appear on operating line
Plant type adapted
. A new configuration is made based on the selected application.