154/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
10 DHW heating
05.02.2007
9
5
Off, Auto
On, Off
7
On, Off
8
On, Off
Cmf, Pcf, Eco, Prt
10
1
On, Off
3
4
6
2
On, Off
On, Off
On, Off
11
3133Z
16
DHW charging
control
DHW operating
mode contact
Resulting operating mode
Legionella, Normal, Reduced, Protection
Pump,
mixing valve etc.
Calendar
Switching program
Resulting operating mode
Normal, Reduced, Protection
Forced charging
with push button
Settings legionella
function
Ti
me s
w
itc
h
Auto, Normal,
Reduced, Protection
Legionella
on, off
Electric immersion heater
Holiday contact
Specual day contact
Interventions
via digital inputs
Operating on the controller,
or via bus
Settings calendar
Special day, holidays
T
im
e swi
tch
Settings 24-hour program,
holiday/special day program
DHW plant operation selector
Wiring test
DHW mode selector
Priority Size
Explanation
Wiring test
During the wiring test (highest priority), the plant
components can be directly controlled, independent
of all other settings
The controller-internal safety functions will
be overridden!
Plant operation selector The plant operation selector has the second highest
priority and can only be overridden by the control-
ler-internal frost protection functions
Electric immersion
heater
When the heat source changes to summer opera-
tion, DHW heating, if installed, will switch over to
the electric immersion heater.
The controller-internal frost protection functions
continue to be ensured. By contrast, the legionella
program will be overridden
Legionella protection
The legionella program can be started in any of the
operating modes, with the exception of preselected
operating mode
“
Protection”
Forced charging
Using button “Forced charging” (DHW push),
recharging to the normal setpoint can be triggered
in any of the operating modes. Forced charging can
also be performed during holiday periods