113/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
9 Heating circuit control
05.02.2007
Operating line
Adjustable values / display / remarks
Heating limit relay
Operating mode relay 1
Operating mode relay 2
* Outside temperature relay:
Only heating circuits 2 and 3 have their own outside temperature. Heating circuit 1 shares the outside tem-
perature with other function blocks in the controller. The outside temperature relay for the outside tempera-
ture of heating circuit 1 is to be configured under
Miscellaneous > Outputs
.
9.2.1 3-position
or
modulating mixing valve
Control of the mixing valve can be accomplished either with a 3-position or DC 0…10 V
actuator. The type of actuator is to be selected via “Extra configuration“.
The output is to be activated via “Extra configuration“:
Main menu >
Commissioning > Extra configuration > Heating circuit 1
(or
2
or
3
)
> Outputs >
Mixing valve 3-pos
Assign terminal
Main menu >
Commissioning > Extra configuration > Heating circuit 1
(or
2
or
3
)
> Outputs >
Mixing valve 3-pos
Assign terminal
9.2.2
Pump control
The heating circuit pump offers the same choices as all the other pumps. An individ-
ual pump can also be monitored; optionally, a twin pump can be used as a heating
circuit pump. For that, the relevant output must be configured.
For more detailed information, refer to section 5.8 “Pump control and twin pumps”.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit 1
(or
2
or
3
)
> Fault settings > Overload pump
Operating line
Range Factory
setting
Fault acknowledgement
None / Acknowledge /
Acknowledge and reset
Acknowledge
and reset
Fault acknowledgement B
None / Acknowledge /
Acknowledge and reset
Acknowledge
and reset
9.3
Operating modes in the heating circuit
9.3.1
Room operating modes
The room operating mode determines the state of a heated room. A differentiation is to
be made between preselected room operating mode and the state of the room operat-
ing mode. Room operating mode
is only available as a preselection.
The user can preselect the following operating modes for space heating:
Extra configuration
Fault settings in the heat-
ing circuit