Ambient conditions
SITOP PSU8200/3800 3ph
92
Manual, 05.2018, C98130-A7638-A1-6-7629
6EP3436-8SB00-0AY0
(24 V/20 A)
6EP3446-8SB10-0AY0
(36 V/13 A)
6EP3446-8SB00-0AY0
(48 V/10 A)
6EP3424-8UB00-0AY0
(12 V/20 A)
6EP3436-8UB00-0AY0
(24 V/17 A)
6EP1437-3BA10
(24 V/40 A)
6EP3437-8SB00-0AY0
(24 V/40 A)
6EP3447-8SB00-0AY0
(48 V/20 A)
6EP3437-8UB00-0AY0
(24 V/40 A)
Damaging gases
Tested according to:
•
EN 60068-2-42 sulfur dioxide
•
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure
Operation:
•
1080 - 795 hPa (-1000 - 2000 m)
•
For operation at altitudes of 2000 - 6000 m above sea
level:
output must be derated by -7.5% / 1000 m or the ambi-
ent temperature must be reduced by 5 K / 1000 m (see
Figure 4-10 Mounting height derating (Page 30))
•
Overvoltage category:
II up to 2000 m (EN 60950-1)
I from 2000 m up to 6000 m (EN 60950-1)
Storage:
•
1080 - 660 hPa (-1000 - 3500 m)