Technical data
6.3 Efficiency
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
71
6.3
Efficiency
6EP3436-8SB00-0AY0
(24 V/20 A)
6EP1437-3BA10
(24 V/40 A)
6EP3437-8SB00-0AY0
(24 V/40 A)
Efficiency at U
out rated
, I
out rated
,
approx.
94 %
92.5 %
94 %
Power loss at U
out rated
,
I
out rated
, approx.
31 W
78 W
73 W
No-load operation power
loss, approx.
3.6 W (PR1), 2.7 W (from
PR2)
7.4 W
3.6 W
Power loss in the "latching
shutdown" state
3.6 W (PR1), 1.7 W (from
PR2)
4.7 W
1.8 W
6EP3446-8SB10-0AY0
(36 V/13 A)
6EP3446-8SB00-0AY0
(48 V/10 A)
6EP3447-8SB00-0AY0
(48 V/20 A)
Efficiency at U
out rated
, I
out rated
,
approx.
94 %
94 %
95 %
Power loss at U
out rated
,
I
out rated
, approx.
30 W
31 W
62 W
No-load operation power
loss, approx.
2.7 W
2.7 W
3.6 W
Power loss in the "latching
shutdown" state
1.7 W
1.7 W
1.8 W
6EP3424-8UB00-0AY0
(12 V/20 A)
6EP3436-8UB00-0AY0
(24 V/17 A)
6EP3437-8UB00-0AY0
(24 V/40 A)
Efficiency at U
out rated
, I
out rated
,
approx.
91 %
94 %
94 %
Power loss at U
out rated
,
I
out rated
, approx.
24 W
26 W
73 W
No-load operation power
loss, approx.
2.7 W
2.7 W
3.6 W
Power loss in the "latching
shutdown" state
1.7 W
1.7 W
1.8 W
Содержание SITOP PSU3800 12 V/20 A
Страница 6: ...Overview SITOP PSU8200 3800 3ph 6 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 52: ...Installation 5 2 Output side connection SITOP PSU8200 3800 3ph 52 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 84: ...Technical data 6 9 Dimension drawing SITOP PSU8200 3800 3ph 84 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 90: ...Safety approvals EMC 7 4 EMC SITOP PSU8200 3800 3ph 90 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 104: ...Applications 9 7 Battery charging with SITOP PSU3800 SITOP PSU8200 3800 3ph 104 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 106: ...Environment SITOP PSU8200 3800 3ph 106 Manual 05 2018 C98130 A7638 A1 6 7629 ...