Technical data
6.2 Output
SITOP PSU8200/3800 3ph
56
Manual, 05.2018, C98130-A7638-A1-6-7629
6.2
Output
6EP3436-8SB00-0AY0
(24 V/20 A)
6EP1437-3BA10
(24 V/40 A)
6EP3437-8SB00-0AY0
(24 V/40 A)
Output
Regulated, isolated DC
voltage
Regulated, isolated DC
voltage
Regulated, isolated DC
voltage
Rated voltage
U
out rated
DC
24 V
24 V
24 V
Total tolerance, static ±
3 %
3 %
3 %
Static line regulation, approx. 0.1 %
0.1 %
0.1 %
Static load regulation, approx. 0.2 %
0.2 %
0.2 %
Residual ripple in the load
range
Peak-peak, max.
100 mV
100 mV
100 mV
Spikes peak-peak, max.
(bandwidth, approx. 20 MHz)
200 mV
200 mV
200 mV
Adjustment range
24 - 28.8 V (PR1)
24 - 28 V (from PR2)
24 - 28.8 V
24 - 28 V
for U
in
< 360 V: 24 - 26 V
Output voltage can be
adjusted
Yes
Yes
Yes
Output voltage setting
•
Remark
Via potentiometer
Max. 480 W
Via potentiometer
Max. 960 W
Via potentiometer
Max. 960 W
Operating display
LED green for "24 V O.K."
LED green for "24 V O.K."
LED green for "24 V O.K."
Signaling
Relay contact (NO contact,
contact rating (isolated):
60 V DC/0.3 A) for "24 V
O.K."
Relay contact (NO contact,
contact rating (isolated):
60 V DC/0.3 A) for "24 V
O.K."
Relay contact (NO contact,
contact rating (isolated):
60 V DC/0.3 A) for "24 V
O.K."
Response when switching
on/off
No overshoot of U
out
(soft
start)
No overshoot of U
out
(soft
start)
No overshoot of U
out
(soft
start)
Starting delay, max.
2.5 s
2.5 s
2 s
Voltage rise, typ.
150 ms
150 ms
150 ms
Rise time of the output
voltage, max.
500 ms
500 ms
500 ms
Rated current I
out rated
20 A
40 A
40 A
Current range
•
Remark
0 - 20 A
60 ... 70 °C derating:
approx. 3 % I
out rated
/K
0 - 40 A
60 ... 70 °C derating:
approx. 4% I
out rated
/K
0 - 40 A
44 A to 45 °C
60 ... 70 °C derating:
approx. 4 % I
out rated
/K
Active power output, typ.
480 W
960 W
1020 W
Constant overload current for
a short circuit when powering
up, typ.
23 A
44 A
51 A
Short-time overload current
for a short circuit in opera-
tion, typ.
60 A
120 A
120 A
Содержание SITOP PSU3800 12 V/20 A
Страница 6: ...Overview SITOP PSU8200 3800 3ph 6 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 52: ...Installation 5 2 Output side connection SITOP PSU8200 3800 3ph 52 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 84: ...Technical data 6 9 Dimension drawing SITOP PSU8200 3800 3ph 84 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 90: ...Safety approvals EMC 7 4 EMC SITOP PSU8200 3800 3ph 90 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 104: ...Applications 9 7 Battery charging with SITOP PSU3800 SITOP PSU8200 3800 3ph 104 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 106: ...Environment SITOP PSU8200 3800 3ph 106 Manual 05 2018 C98130 A7638 A1 6 7629 ...